This completes the steps required to allow a paralleled circuit to the auto-run mode that will enable the high voltage power supply when activated by the manual button.
Note: Leave all existing wiring; it is not necessary to remove any of the old contacts or wires.
20. Motor Control Board
Motor Control Board Overview
21. 12 Volt Power Supply
The 12-volt DC power supply is responsible for supplying power for the 12-volt DC relays, detector circuit board, flaw light, timer over light (test over light), start button, and safety contacts. The 12-volt DC power supply is protected by the 1-amp breaker. To check the 12-volt DC power supply check that the line voltage to the power supply is 120 VAC at the 1-amp breaker. Next, check the DC output is 12 volts.
A quick way to check if the power supply is working can be accomplished by pressing the flaw light lens, or the timer complete light (test over) lens . When either of these lenses are pressed the light should illuminate. If the light illuminates the 12-volts DC power supply should be considered good.
The 12-volt DC power supply is either din rail mounted (H40-0029) or mounted in an aluminum frame (H40-0030). Click the part numbers to see which one you have.
27. Arm Swing In/Out
The normally open contact is used to supply 120 VAC to the arm swing in/out solenoid and to the Inside UP/Down switch. If the probe does not swing into the tire, the normally open contact may not be allowing electricity to pass. Ensure that the selector is set to the in position, electricity should be on both sides of the normally open contact. If electricity is not on both sides of the contact than replace the contact. Note, the probe will not go up or down if, the arm swing contact is not working.
Additionally, if the probe will not swing in or is mushy check the slow start.
32. Flaw Light – Diagnosing a Faulty Detector Circuit
The Flaw Light is designed to alert the operator of a flaw condition in a tire casing. Additionally, the flaw light can be useful in diagnosing issues with the NDT. The following checks can be made to diagnose a faulty detector circuit board using the flaw light. Any deviation from the following conditions signifies a defective detector circuit:
The flaw light should be illuminated when the probe is up and out of the tire.
- When the probe is initially swung in and down the flaw light should remain on until the start button is pressed.
- When the start button is pressed the flaw light will turn off, the motor should begin turning, and the high voltage should turn on.
- When the detector circuit finds a flaw the flaw light will illuminate.
- When the probe is lifted to the up and out position, the flaw light will illuminate.
33. Motor Speed Control
To ensure that the 50 K potentiometer is not defective a meter capable of detecting resistance is necessary. Disconnect the white wire that routes from the motor control board to the potentiometer. It is best to disconnect the wire at the motor control board, rather than de-soldering it from the potentiometer. Set a meter to check resistance. With one lead from the meter attached to the disconnected white wire, and attach the other meter lead to the black wire where it soldered to the potentiometer. Next, watch the display on the meter while tuning the knob of the potentiometer. If an open is displayed than the potentiometer is defective, and is the reason the motor does not work. If the potentiometer displays varying resistances ranging from 0 ohms to 50 k ohms, the potentiometer is not defective.
34. Test Over or Timer Over Light
This light uses a 12-volt DC bulb (H49-0027), and will illuminate when the detector board’s timer runs out. This light does not signify that a tire being inspected has received a complete inspection. The light is signifies that the timer has completed counting down or up, depending on the type of detector circuit installed. The Test Over / Timer over Light is installed for safety reasons. For example, if the start button was pressed and the operator leaves his station, the machine would automatically stop after 30 seconds or less.
35. 12 Volt DC Relay
There are two identical 12 VDC relays in the NDT. Both relays use a 12 VDC solenoid, powered by the 12 VDC power supply. There is always 12 VDC positive going to the solenoid. However, the only time 12 VDC negative will be available for the solenoid is when the detector circuit feeds the 12 VDC negative to the relay. The detector circuit will only send the 12VDC negative voltage to the solenoid if the probe is in a tire to be inspected.
36. 1-Amp Circuit Breaker
The 1-Amp circuit breaker protects the 12 VDC power supply. The 1-amp circuit breaker feeds 120 VAC to the primary of the 12VDC power supply.
37. 2-Amp Circuit Breaker
The 2-amp circuit breaker protects the 50 KV power supply. If there is no high voltage the first place to check is the 2-amp circuit breaker to ensure it has not been disengaged. If the circuit breaker is disengaged that signifies that there is something wrong with the high-voltage circuit. Usually, this means that that one of the following has failed: 1) the 50 KV power supply, 2) the 1 Meg or 20 Meg resistor, or 3) either of the capacitors. Do not continue to operate the NDT if the 2-amp circuit breaker disengages without examining the cause.
42. Air Solenoid Probe In/Out
Electricity from the arm swing in/out contact supplies this solenoid with power. If power is reaching the solenoid when the arm swing contact is in the “In” position check if air is passing through the valve that the solenoid is connected.
44. Air Valve for Probe In/Out or Up/Down - Air Kit 1 Instructions, Air Kit 2 Instructions, and Air Kit 3 Assy Instructions.
On the In/Out valve, air is routed through the middle port on the side of the valve that has three ports. The other side of the valve has two ports and one port is for air to push the probe into the tire, the other port is for air to push the probe out of the tire.
45. Air Regulators for ProbeAir Kit 1 Instructions, Air Kit 2 Instructions, and Air Kit 3 Assy Instructions.
48. Slow Start
If the slow start is not working properly, the swing arm/probe may not swing in, out, up, or down very effectively. Follow the instructions to adjust the slow start.
52. 31-10 BnC
The 31-10 BnC Connector is part of the Current Transformer. The wires that connect to this connector are polarity sensitive.
On older NDT machines where the Current Transformer is mounted to the Mast Swing Arm, there are two yellow wires soldered to the 31-10 BnC Connector. One of the wires is colored black with a permanent marker. It is critical that this wire be soldered to the outside pin of the BnC connector. If the wires are soldered to terminals on the BnC connector so that the polarity is backwards, or if solder shorts the terminals of the BnC the Specific Frequency will not be sent to the detector board and flaws will be missed.
53. Reverse Relay Assy

Reverse Relay Assembly

Breaking Resistor

Motor Control Board with Alternative Breaking Resistor
If the motor stops working it could be a number of reasons. However, check the brushes of the motor. There are two brushes that could cause the motor to stop working. The motor is a 90 VDC motor. If 90 VDC or less is applied directly to the motor, the motor should turn if it is not defective.
Depending on the construction of the tire (steel or bias) the NDT can detect the following:
Steel Belted
- Through holes that are between the probe chain bar and the ground roller (A)
- Partial holes inside the tire that extend to the steel belts (B)
- Partial holes between the steel belts of the tire and the ground roller (C)

Bias Ply
- Through holes that are between the probe chain bar and the ground roller (A).
- Embedded objects that touch either the chain bar or the ground roller (B and C).

Questions on Repetition (no electrical arcing)
I have an NDT that did not arc to an obvious flaw why not?
Hawkinson—If potential exists for electricity to arc to a flaw the NDT will arc every time. If the NDT did not arc than no potential existed. After checking the NDT for mechanical failure the next step is to analyze other reasons why an NDT will not arc to a flaw:
- When a tire is spread on the NDT, the degree of spread can vary. When a tire is spread, flaws can open, or flaws can close. If a flaw closes tightly it is possible that potential to arc does not exist, therefore, no arc will occur.
- A conductive object is imbedded within the tire and surrounded by nonconductive properties. There is no potential for an arc of electricity to occur therefore no arc. (This problem can be reduced by adding an NDT after the buffer or as a final inspection unit. Occasionally, an imbedded piece of metal will be missed by the NDT and will be forced out of position by the buffer or a pressure chamber. Materials, labor, and adjustments can be reduced by adding NDTs to inspect tires after buff and during final inspection.
- If the probe or ground roller does not touch the flaw, no potential can exist. (This problem is typical. Sidewall wires on the probe become deformed and do not touch parts of the tire. Replacing sidewall wires regularly can reduce missed flaws.)
- The rotation speed of the tire causes a flaw to pass under the probe when no electricity was available to arc--The NDT makes a distinct ticking sound as high voltage is applied. When a ticking sound is heard, electricity is applied to the tire. Between ticks, no electricity is applied to the tire. The slower the NDT rotates the likelihood of an arc to occur is greater. The average time to “electrically” inspect a tire is less than 32 seconds. However, most retreaders who use the NDT also use it to conduct a visual inspection and some use the NDT to make repairs to the tire at the same time as inspection. Install a manager’s speed kit to ensure your operator does not electrically inspect tires too fast - Motor Speed Kit 1, Motor Speed Kit 2.
The NDT is a tool and requires a well-trained operator to maximize the NDT guarantee.
Questions on Repetition (automatic mode arcing observed)
The NDT arced but did not stop automatically while in the start (automatic) mode. How to Detect a defective detector circuit board.
Hawkinson—From time to time this phenomenon will happen, hence the importance to remember the NDT is a tool and requires a well-trained operator to maximize the NDT guarantee. Here are some facts the operator of the NDT should be aware of:
- The NDT makes a distinct sound when an arc occurs. Therefore, if an arc is heard or seen, but the NDT does not automatically stop, the operator must manually stop the tire rotation and use the manual mode of the NDT to locate and investigate the flaw.
- When two or more flaws are located within close proximity of each other, the detector of the NDT may not be quick enough to stop for the first hole but may stop for the last.
- The NDT arced to a large obvious flaw but did not stop. This can occur because the NDT was designed to find flaws that are small and not visible to the eye. An arc to a small flaw causes the currant flow to rise and fall quickly. This quick change in currant is how the detector determines a flaw exists. Therefore, a rapid rise in current that remains high [large hole] and does not fall quickly will not trigger the detector.
A number of variables may cause the NDT to miss a nail hole when the start (automatic) mode is used. The NDT was designed to maximize the NDT guarantee using a well-trained operator who must be aware of NDT performance limitations.
Questions on Reliability
Hawkinson—Test tires are NOT an effective way to determine the NDT’s reliability. Typically, test tires are created by drilling or puncturing holes in a tire. Drilling or puncturing a hole in a tire will cause a very clean hole. Whereas, a tire that is punctured by a nail on the road will collect contaminates, which may contain conductive material and will push the nail in and out of the tire many times. The best way to test the reliability of the NDT should be accomplished by conducting the spark test. The spark test is explained in the owner’s manual. The NDT guarantees that the NDT will reduce the adjustment rate compared to visual inspection alone.
How can the NDT save money?
Customer—Can the NDT save me money?
Hawkinson—Compare the cost of the NDT to the cost of adjustments. Tests conducted by an independent consultation service proved that the NDT will find flaws in tires that are missed during visual inspection. In fact, the independent testing services concluded that the NDT would find significantly more flaws in tires compared to visual inspection. Compare the NDT to other types of inspection equipment such as shearography, x-ray, or ultrasound and the NDT will be the most affordable, efficient, and reliable machine. The upfront cost of the NDT is less than many of the other inspection methods and long-term maintenance is typically minimal. Labor costs are less than many other inspection methods. Production costs can be reduced; reducing the number of times buffer blades must be replaced from missed objects in the tire; the amount of material waste due to undetected flaws is reduced. The NDT is durable and dependable and has been the standard in North America for the last 20 years. See NDT Payback Page
My machine is missing flaws, what is wrong?
The following describes a sequential and logical order of trouble shooting the NDT and is common for all model NDT machines.
First, check the high-voltage cabinet to ensure that the critical frequency is good. Measure the 1 Meg, 20 Meg, 75 Ohm, 5 K Ohm, and 150 Ohm resistors (How to measure the resistors), measure the High-Voltage Coil, clean and cycle the High-Voltage Relays, gap the Capacitors (How to gap the capacitors).
Wipe down the cabinet and vacuum out all of the dust and debris. If there is corrosion, install an NDT-Kit, Hawkinson Part Number H05-0008. Install an NDT-Kit once every five years or as needed.
Check the 2-amp breaker to ensure that the breaker did not disengage. If the breaker is disengaged, click on the Hyperlink for the 2-amp breaker.
Check that the coax cable, current transformer, and detector board cables are all connected, and there is no obvious damage. If damage is noted, or questionable, click on the Hyperlink for a specific component for specific directions.
Check that the probe is in alignment.
Try a spark test (spark test directions).

High-Voltage Cabinet Overview
There are many companies that use the Hawkinson NDT to ensure that their retreaded tires are of the highest quality. For example:
Michelin
Please take a look at this link and download the Nail Hole Inspection video.
Wingfoot / Goodyear
The link shows a picture of the NDT-II made by Hawkinson, which is used by Goodyear.
Bridgestone / Bandag
The link below shows the NDT-IIB being used by in Bandag's retread process at approximately the 2:00 minute mark.
What maintenance should I do to the NDT?
NDT® User Maintenance (User Maintenance Schedule)
Probes should be vertical, centered in the tire, and properly placed over the metal drive roller.
Air should be set to specs as per operator’s manual. Never adjust air pressure to compensate for dirty, sticking V-bearings.
Worn and broken items such as sidewall wires, plastic paddles, roller bearings, spread rollers, and key chains hinder performance of the NDT®. It is not necessary to over-tighten the screws that hold the sidewall wires in place.
Inspect the NDT® for broken, worn, or wearing parts. Do not wait for a worn part to fail before replacement.
Pay close attention to:
- high voltage wires
- black coaxial cable
- loose screws
- tie-wraps
- ground straps
- resistors
- switch activators and contacts
The back cabinet contains high voltage parts, which can wear and should be checked. USE CAUTION! Speak to a Paul E. Hawkinson® technician before entering this cabinet.
Basically, there are two functions of the NDT® that allow it to find flaws in tire casing:
- Voltage is applied to the casing that creates an electrical arc when a flaw is present.
- The detector circuitry senses electrical current changes when an arc occurs.
The gap between the carbon balls in the high-voltage cabinet is the only adjustment the user has control over that can affect the current applied to a tire casing. The gap should be 11/16 inch. Speak to a technician before attempting to measure or adjusting the gap.
Sensitivity is adjusted by a potentiometer located on the detector circuit board. Hawkinson presets this at 4 volts on older detector circuit boards, and 1.654 on new detector circuit boards.
A clean machine works better and looks better. Follow these suggestions for proper NDT maintenance:
Engine de-greaser works well for cleaning the drive roller, v-rails, and other parts where heavy gunk collects.
The Start Button does not work, why?
This is a common problem with the NDT and is usually a simple problem to fix. Typically, the problem occurs because there is a small pinhole in the probe wire, or the high-voltage output wire. Replacing these two wires nearly always fixes the problem.
If the problem continues to persist after replacing the probe wire and high-voltage output wire, the machine may have a defective detector circuit board. To check the detector board, disengage the 2-amp breaker in the operator’s console. Next, place a tire on the machine, and begin the electronic inspection. When the Start Button is pressed, the yellow flaw light turns off and the motor should turn. There will be no high-voltage. However, the motor should turn, and the green timer over light (Test Complete) should illuminate after approximately 30 seconds. If this is, the case detector board is not the problem.
However, if the motor does not turn check the 12-volt DC power supply, and 12-volt DC relays, and cables between the detector circuit board and operators console. If they are good, replace the detector circuit board.
If all else fails replace the coax cable, and if the problem persists, the only other component that can cause this situation is the current transformer, so replace that as well.
My motor won’t turn, why?
Six systems can cause the motor to stop turning. Five of the six can be analyzed, and by process of elimination, the sixth can be diagnosed.
First, check the 12-volt relays, and 12-volt power supply. Next, check the 50 K potentiometer. Next, check the direction switches on the operator’s console, then on the front remote location. Next, check the motor contactors (not all NDT machines have motor contactors). Finally, check the motor. If all of the aforementioned parts are good, replace the motor control board.
Critical Frequency
Imagine the high voltage cabinet as a radio. The radio transmits a specific frequency, which is created by the high-voltage power supply, resistors, and gapping of the capacitors. The specific frequency travels up the antenna, which is the high-voltage output wire to the tire. A receiver, which is the current transformer, intercepts the specific frequency and sends the signal through the coax cable to the detector circuit. The detector circuit listens for changes to the specific frequency. When an arc occurs, the detector circuit realizes a change has occurred, which then triggers a flaw condition. If an arc occurs anywhere along the antenna, the detector will trigger a flaw condition. The arc does not have to occur in the tire.